Comprehensive industrial-grade technical specifications compiled directly from Invinity Data Sheets to satisfy the demanding requirements of B2B customers, grid engineers, and EPC specialists.
Based on official Invinity engineering technical data, providing detailed parameters for both Utility-Scale and Commercial & Industrial (C&I) flagship storage systems:
| Technical Parameters | Endurium™ (Utility-Scale Grid Storage) | Endurium Enterprise™ (C&I Behind-the-Meter) |
|---|---|---|
| System Architecture | 4x Endurium Modules form 1 "String", incorporating String Control Units (SCU) and high-voltage string cabling. | 2x Endurium Modules form 1 "String", incorporating String Control Units (SCU) and inter-string cabling. |
| Max DC Power | 500 kW/ String |
250 kW/ String |
| Max Usable DC Energy | 2,065 kWh |
1,030 kWh |
| Discharge Duration | Continuous deep dispatch from 3 to 18 hours | Flexible dispatch from 3 to 18 hours for C&I peak shaving & backup |
| Constant Power Profiles | 3h @470 kW 6h @302 kW 8h @238 kW 12h @169 kW |
4h @200 kW 6h @151 kW 8h @119 kW 12h @84 kW |
| Max DC Round Trip Efficiency | Max DC RTE: 73% (Max total RTE 68%) | Max DC RTE: 73% (Max total RTE 68%) |
| DC Voltage & Current | 800–1,280 VDC Max DC Current 600A |
400–640 VDC (with EPC CAB1000) Max DC Current 600A |
| DC Response Time | <15 ms from Hotstandby <1 min from Off |
<15 ms from Hotstandby <1 min from Off |
| Operating Environment | Ambient Temp -10ºC to 45ºC Humidity 5-95% Max Altitude 2,000m |
Ambient Temp -10ºC to 45ºC Humidity 5-95% Max Altitude 2,000m |
| Enclosure & Footprint | IP 54 Rating | String Footprint 93.7 m² (Energy Density 130 MWh/Acre) Module Dim: 6.1m x 2.4m x 2.9m (36,000 kg) |
IP 54 Rating | String Footprint 50.5 m² (Energy Density ~95 MWh/Acre) Module Dim: 6.1m x 2.4m x 2.9m (36,000 kg) |
| 3D Stackability | High-density 3-layer vertical stacking (~8.7m height) with zero clearance buffer required, maximizing land efficiency.. | High-density 3-layer vertical stacking (~8.7m height) with zero clearance buffer required, maximizing land efficiency.. |
| Certifications & Standards | CE, UL 1973, UL 9540A, Sub Assembly under UL 9540, NFPA, IEC 62933 | CE, UL 1973, UL 9540A, Sub Assembly under UL 9540, NFPA, IEC 62933 |
| Lifespan & Degradation | 30–35+ Years operating life with unlimited cycling (<0.2%/yr fade) | 30–35+ Years operating life with unlimited cycling (<0.2%/yr fade) |
Unlike lithium-ion batteries (5-10 year lifespan requiring 2-3 cell swaps over 25 years), vanadium flow batteries deliver 30 to 35+ years of reliable operation with unlimited cycling. Proven by 27,000 hours of field testing with 0% capacity degradation.
Utilizes water-based liquid electrolyte, physically eliminating thermal runaway, fire, and explosion hazards. Fully complies with latest fire safety guidelines, qualifying for exemption from automatic water spray/sprinkler requirements.
Over 99% of components are recyclable. The liquid vanadium electrolyte retains 100% of its chemical properties forever and can be reused infinitely.
Access full engineering parameters, voltage operating curves, dimension drawings, and DNV bankability summary reports by downloading the official PDF files: